EEV Selection Instructions

Valve Selection: Run the selection with the highest condenser temperature and corresponding liquid temperature the system will experience during the year. Run the selection again with the lowest condenser temperature and corresponding liquid temperature the system will experience during the year. Select the valve that is in the 35 to 65% range, or closest to it, under BOTH conditions.

Distributor & High Side ∆P: R134a, R409A Total pressure drop averages in the range of 25-35 psi (1.7-2.4 bar).

R22, R404A, R407C, R422A, R422D, R438A, R448A, R449A, R454A, R454B, R454C, R455A, R466A, R507 Total pressure drop averages in the range of 35-45 psi (2.4-3.1 bar).

R410A, R744 Total pressure drop should be in the range of 45-55 psi (3.1-3.8 bar).